WebMay 7, 2013 · NFPA 54 7.13.2 IFGC 310.1.1 IRC G2511.1.1 CSST gas piping systems shall be bonded to the electrical service grounding electrode system. The bonding jumper shall connect to a metalic pipe or fitting BETWEEN THE POINT OF DELIVERY AND THE FIRST DOWNSTREAM CSST FITTING. WebCSST shall be considered to be bonded when it is connected to appliances that are connected to the appliance grounding conductor of the circuit supplying that appliance. 7.13.2 CSST. CSST gas piping systems shall be bonded to the electrical service grounding electrode system at the point where the gas service enters the building. The
SECTION G2411 (310) ELECTRICAL BONDING
WebScope. 1.1. This Standard applies to fuel gas piping systems using corrugated stainless steel tubing (CSST), intended for installation in residential, commercial or industrial buildings, and including the following components as a minimum: a) Corrugated stainless steel tubing (CSST); b) Fittings for connection to the CSST; and. WebSep 12, 2013 · The bonding jumper shall connect to a metallic pipe or fitting between the point of delivery and the first downstream CSST fitting. The bonding jumper shall be not smaller than 6 AWG copper wire or equivalent. Gas piping systems that contain one or more segments of CSST shall be bonded in accordance with this section. durungaling aboriginal hostel
Arc-Resistant Jacketed CSST UpCodes
WebJan 13, 2010 · Here's what NYS requires: “G2411.2 (310.2) Gas pipe bonding - systems that contain CSST.A gas piping system that contains any corrugated stainless steel tubing (CSST) shall be electrically continuous and shall be bonded to the electrical service grounding electrode system at the point where the gas service enters the building or … WebCSST is listed in the World's largest and most authoritative dictionary database of abbreviations and acronyms CSST - What does CSST stand for? The Free Dictionary WebThe bonding jumper shall connect to a metallic pipe or fitting between the point of delivery and the first downstream CSST fitting. The bonding jumper shall be not smaller than 6 … durst family medicine sullivan\\u0027s island